Section 7. Installation
83
Power supplies available from Campbell Scientific can be reviewed in the
appendix
Power Supplies
(p. 542),
or at
www.campbellsci.com
. Contact a Campbell
Scientific application engineer if assistance in selecting a power supply is needed,
particularly with applications in extreme environments.
7.4.1 CR800 Power Requirement
The CR800 operates on dc voltage ranging from 9.6 to 16 Vdc. It is internally
protected against accidental polarity reversal. A transient voltage suppressor
(TVS) diode on the
12-Vdc power input terminal
(p. 35)
provides transient
protection by clamping voltages in the range of 19 to 21 V. Sustained input
voltages in excess of 19 V can damage the TVS diode.
Caution
The
12V
and
SW12
terminals on the wiring panel are not regulated by
the CR800; they are at the same voltage levels as the CR800 primary power
supply. When using the CR800 wiring panel to source power to other 12-Vdc
devices, be sure the power supply regulates the voltage within the range specified
by the manufacturer of the connected device.
7.4.2 Calculating Power Consumption
Read More!
Power Requirements
(p. 64).
System operating time for batteries can be determined by dividing the battery
capacity (ampere-hours) by the average system current drain (amperes). The
CR800 typically has a quiescent current draw of 0.5 mA (with display off), 0.6
mA with a 1-Hz sample rate, and >10 mA with a 100-Hz sample rate. With the
external keyboard / display on, an additional 7 mA is added to the current drain
while enabling the backlight for the display adds 100 mA to the current drain.
7.4.3 Power Supplies
The appendix
Power Supplies
(p. 542)
lists external power supplies available from
Campbell Scientific, including alkaline and solar options. More information is
available in manual or brochure form at
www.campbellsci.com
.
7.4.3.1 External Batteries
When connecting external power to the CR800, remove the green
POWER IN
connector from the CR800 face. Insert the positive 12-Vdc lead into green
connector terminal
12V
. Insert the ground lead in green connector terminal
G
.
Re-seat the green connector into the CR800. The CR800 is internally protected
against reversed external-power polarity. Should this occur, correct the wire
connections.
7.4.4 Vehicle Power Connections
If a CR800 is powered by a motor-vehicle power supply, a second power supply
may be needed. When starting the motor of the vehicle, battery voltage often
drops below 9.6 Vdc. This causes the CR800 to stop measurements until the
voltage again equals or exceeds 9.6 Vdc. A second supply can be provided to
prevent measurement lapses during vehicle starting. The figure
Connecting
CR800 to Vehicle Power Supply
(p. 84)
illustrates how a second power supply
Содержание CR850
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 26: ...Table of Contents 26...
Страница 30: ...Section 2 Cautionary Statements 30...
Страница 32: ...Section 3 Initial Inspection 32...
Страница 35: ...Section 4 Quickstart Tutorial 35 Figure 2 Wiring panel...
Страница 55: ...Section 4 Quickstart Tutorial 55 Figure 24 PC200W View data utility...
Страница 78: ...Section 5 System Overview 78...
Страница 80: ...Section 6 CR800 Specifications 80...
Страница 95: ...Section 7 Installation 95 Figure 35 DevConfig OS download window Figure 36 Dialog box confirming OS download...
Страница 104: ...Section 7 Installation 104 Figure 43 Include File settings via DevConfig Figure 44 Include File settings via PakBusGraph...
Страница 267: ...Section 7 Installation 267 Figure 84 Running average signal attenuation...
Страница 268: ...Section 7 Installation 268...
Страница 384: ...Section 8 Operation 384 Figure 113 Using the keyboard display...
Страница 385: ...Section 8 Operation 385 8 8 1 Data Display Figure 114 Displaying data with the keyboard display...
Страница 387: ...Section 8 Operation 387 Figure 116 Real time custom...
Страница 388: ...Section 8 Operation 388 8 8 1 3 Final Storage Tables Figure 117 Final storage tables...
Страница 389: ...Section 8 Operation 389 8 8 2 Run Stop Program Figure 118 Run Stop Program...
Страница 390: ...Section 8 Operation 390 8 8 3 File Display Figure 119 File display...
Страница 396: ...Section 8 Operation 396...
Страница 402: ...Section 9 Maintenance 402...
Страница 450: ...Section 11 Glossary 450...
Страница 504: ...Appendix A CRBasic Programming Instructions 504...
Страница 526: ...Appendix B Status Table and Settings 526...
Страница 530: ...Appendix C Serial Port Pinouts 530...
Страница 536: ...Appendix E FP2 Data Format 536...
Страница 550: ...Appendix F Other Campbell Scientific Products 550...
Страница 564: ...Index 564 WriteIO 464 Writing Program 108 X XML 448 XOR 473 Y Y intercept 141 142 Z Zero 155 166 Zero Basis 151...
Страница 565: ......