Section 7. Installation
177
Serial number = 101
Start Measurement Commands (aM! & aC!)
A measurement is initiated with
M!
or
C!
commands. The response to each
command has the form
atttnn
, where
•
a
= sensor address
•
ttt
= time, in seconds, until measurement data are available
•
nn
= the number of values to be returned when one or more subsequent
D!
commands are issued.
Start Measurement Command (aMv!)
Qualifier
v
is a variable between 1 and 9. If supported by the sensor
manufacturer, v requests variant data. Variants may include:
•
alternate units (for example, °C or °F)
•
additional values (e.g., level and temperature)
•
diagnostic of the sensor’s internal battery
Example:
Command:
5M!
Response:
500410
(
atttnn
,
indicates
address
5,
data
ready
in
4
seconds,
will
report
10
values).
Example:
Command:
5M7!
Response:
500201
(
atttnn
indicates
address
5,
data
ready
in
2
seconds,
will
report
1
value).
v
=
7
instructs
the
sensor
to
return
the
voltage
of
its
internal
battery.
Start Concurrent Measurement Command (aC!)
Concurrent measurement allows the CR800 to request a measurement, continue
program execution, and pick up the requested data on the next pass through the
program. A measurement request is then sent again so data are ready on the next
scan. The datalogger scan rate should be set such that the resulting skew between
time of measurement and time of data collection does not compromise data
integrity.
Note
This command is new to Version 1.2 or higher of the SDI-12 Specification.
Older sensors, older loggers, or new sensors that do not meet v1.2 specifications
will likely not support this command
Aborting a Measurement Command
A measurement command (
M!
or
C!
) is aborted when any other valid command is
sent to the sensor.
Содержание CR850
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 26: ...Table of Contents 26...
Страница 30: ...Section 2 Cautionary Statements 30...
Страница 32: ...Section 3 Initial Inspection 32...
Страница 35: ...Section 4 Quickstart Tutorial 35 Figure 2 Wiring panel...
Страница 55: ...Section 4 Quickstart Tutorial 55 Figure 24 PC200W View data utility...
Страница 78: ...Section 5 System Overview 78...
Страница 80: ...Section 6 CR800 Specifications 80...
Страница 95: ...Section 7 Installation 95 Figure 35 DevConfig OS download window Figure 36 Dialog box confirming OS download...
Страница 104: ...Section 7 Installation 104 Figure 43 Include File settings via DevConfig Figure 44 Include File settings via PakBusGraph...
Страница 267: ...Section 7 Installation 267 Figure 84 Running average signal attenuation...
Страница 268: ...Section 7 Installation 268...
Страница 384: ...Section 8 Operation 384 Figure 113 Using the keyboard display...
Страница 385: ...Section 8 Operation 385 8 8 1 Data Display Figure 114 Displaying data with the keyboard display...
Страница 387: ...Section 8 Operation 387 Figure 116 Real time custom...
Страница 388: ...Section 8 Operation 388 8 8 1 3 Final Storage Tables Figure 117 Final storage tables...
Страница 389: ...Section 8 Operation 389 8 8 2 Run Stop Program Figure 118 Run Stop Program...
Страница 390: ...Section 8 Operation 390 8 8 3 File Display Figure 119 File display...
Страница 396: ...Section 8 Operation 396...
Страница 402: ...Section 9 Maintenance 402...
Страница 450: ...Section 11 Glossary 450...
Страница 504: ...Appendix A CRBasic Programming Instructions 504...
Страница 526: ...Appendix B Status Table and Settings 526...
Страница 530: ...Appendix C Serial Port Pinouts 530...
Страница 536: ...Appendix E FP2 Data Format 536...
Страница 550: ...Appendix F Other Campbell Scientific Products 550...
Страница 564: ...Index 564 WriteIO 464 Writing Program 108 X XML 448 XOR 473 Y Y intercept 141 142 Z Zero 155 166 Zero Basis 151...
Страница 565: ......