Section 7. Installation
190
7.8.5.1 OutputOpt Parameters
In the CR800
WindVector()
instruction, the
OutputOpt
parameter defines the
processed data that are stored. All output options result in an array of values, the
elements of which have
_WVc(n)
as a suffix, where
n
is the element number. The
array uses the name of the
Speed/East
variable as its base. table
OutputOpt
Options
(p. 190)
lists and describes
OutputOpt
options.
Table 29.
OutputOpt Options
Option
Description (WVc() is the Output Array)
0
WVc(1): Mean horizontal wind speed (S)
WVc(2): Unit vector mean wind direction (
Θ
1)
WVc(3): Standard deviation of wind direction
σ
(
Θ
1). Standard deviation is
calculated using the Yamartino algorithm. This option complies with EPA
guidelines for use with straight-line Gaussian dispersion models to model plume
transport.
1
WVc(1): Mean horizontal wind speed (S)
WVc(2): Unit vector mean wind direction (
Θ
1)
2
WVc(1): Mean horizontal wind speed (S)
WVc(2): Resultant mean horizontal wind speed (U)
WVc(3): Resultant mean wind direction (
Θ
u)
WVc(4): Standard deviation of wind direction
σ
(
Θ
u). This standard deviation is
calculated using Campbell Scientific's wind speed weighted algorithm. Use of the
resultant mean horizontal wind direction is not recommended for straight-line
Gaussian dispersion models, but may be used to model transport direction in a
variable-trajectory model.
3
WVc(1): Unit vector mean wind direction (
Θ
1)
4
WVc(1): Unit vector mean wind direction (
Θ
1)
WVc(2): Standard deviation of wind direction
σ
(
Θ
u). This standard deviation is
calculated using Campbell Scientific's wind speed weighted algorithm. Use of the
resultant mean horizontal wind direction is not recommended for straight-line
Gaussian dispersion models, but may be used to model transport direction in a
variable-trajectory model.
7.8.5.2 Wind Vector Processing
WindVector()
uses a zero-wind-speed measurement when processing scalar wind
speed only. Measurements at zero wind speed are not used in vector speed or
direction calculations (vectors require magnitude and direction).
This means, for example, that manually-computed hourly vector directions from
15-minute vector directions will not agree with CR800-computed hourly vector
directions. Correct manual calculation of hourly vector direction from 15-minute
vector directions requires proper weighting of the 15-minute vector directions by
the number of valid (non-zero wind speed) wind direction samples.
Note
Cup anemometers typically have a mechanical offset which is added to each
measurement. A numeric offset is usually encoded in the CRBasic program to
compensate for the mechanical offset. When this is done, a measurement will
equal the offset only when wind speed is zero; consequently, additional code is
Содержание CR850
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 26: ...Table of Contents 26...
Страница 30: ...Section 2 Cautionary Statements 30...
Страница 32: ...Section 3 Initial Inspection 32...
Страница 35: ...Section 4 Quickstart Tutorial 35 Figure 2 Wiring panel...
Страница 55: ...Section 4 Quickstart Tutorial 55 Figure 24 PC200W View data utility...
Страница 78: ...Section 5 System Overview 78...
Страница 80: ...Section 6 CR800 Specifications 80...
Страница 95: ...Section 7 Installation 95 Figure 35 DevConfig OS download window Figure 36 Dialog box confirming OS download...
Страница 104: ...Section 7 Installation 104 Figure 43 Include File settings via DevConfig Figure 44 Include File settings via PakBusGraph...
Страница 267: ...Section 7 Installation 267 Figure 84 Running average signal attenuation...
Страница 268: ...Section 7 Installation 268...
Страница 384: ...Section 8 Operation 384 Figure 113 Using the keyboard display...
Страница 385: ...Section 8 Operation 385 8 8 1 Data Display Figure 114 Displaying data with the keyboard display...
Страница 387: ...Section 8 Operation 387 Figure 116 Real time custom...
Страница 388: ...Section 8 Operation 388 8 8 1 3 Final Storage Tables Figure 117 Final storage tables...
Страница 389: ...Section 8 Operation 389 8 8 2 Run Stop Program Figure 118 Run Stop Program...
Страница 390: ...Section 8 Operation 390 8 8 3 File Display Figure 119 File display...
Страница 396: ...Section 8 Operation 396...
Страница 402: ...Section 9 Maintenance 402...
Страница 450: ...Section 11 Glossary 450...
Страница 504: ...Appendix A CRBasic Programming Instructions 504...
Страница 526: ...Appendix B Status Table and Settings 526...
Страница 530: ...Appendix C Serial Port Pinouts 530...
Страница 536: ...Appendix E FP2 Data Format 536...
Страница 550: ...Appendix F Other Campbell Scientific Products 550...
Страница 564: ...Index 564 WriteIO 464 Writing Program 108 X XML 448 XOR 473 Y Y intercept 141 142 Z Zero 155 166 Zero Basis 151...
Страница 565: ......