Appendix H. Foundation Fieldbus communication
H.1 Introduction
Fieldbus is a bi-directional digital communication
protocol for field devices, which offers an advancement
in technologies for process control systems and is widely
employed by numerous field devices.
The XMT1000 FF option is designed to the specification
standardized by the Fieldbus Foundation, and provides
interoperability with devices produced by other
manufacturers. The Fieldbus option PCB comes with
software consisting of five AI function blocks and one PID
function block.
Note:
For more general information on other features,
engineering, design, construction work, startup and
maintenance of Fieldbus, refer to Fieldbus Technical
Information (TI 38K3A01-01E).
H.2 Installation
H.2.1 Network configuration
The following instruments are required for use with Fieldbus
devices:
•
Power supply:
Fieldbus requires a dedicated power
supply. It is recommended that current capacity be well
over the total value of the maximum current consumed
by all devices (including the host). Conventional DC
current cannot be used as is.
•
Terminators:
Fieldbus requires two terminators. Refer to
the supplier for details of terminators that are attached
to the host.
•
Field devices:
Connect the field devices necessary
for instrumentation. XMT1000 has passed the
interoperability test conducted by the Fieldbus
Foundation. To properly start Fieldbus, use devices that
satisfy the requirements of the above test.
•
Host:
Used for accessing field devices. A dedicated
host (such as DCS) is used for an instrumentation line
while dedicated communication tools are used for
experimental purposes.
H.2.2 Polarity
The XMT1000 Foundation Fieldbus terminals are marked
(+) and (-). However, the design is polarity insensitive.
This means the XMT1000 will communicate even if the
connections are reversed.
H.2.3 Connection
Connect the Fieldbus wires to P1 on the terminal PCB (see
Figure 127 below). Panametrics recommends using the top
right rear port on the enclosure.
IMPORTANT:
Please make sure to follow all local installation guidelines.
Figure 127: FF Connection to XMT1000
105
Содержание Panametrics PanaFlow LC
Страница 1: ...PanaFlow LC User s manual 910 327 Rev A...
Страница 2: ...ii...
Страница 3: ...PanaFlow LC Panametrics liquid ultrasonic flowmeter User s manual 910 327 Rev A Sep 2019 iii...
Страница 4: ...no content intended for this page iv...
Страница 12: ...no content intended for this page xii...
Страница 44: ...Figure 58 Setting up pulse output 32...
Страница 49: ...Figure 60 Setting up alarm output 37...
Страница 80: ...no content intended for this page 68...
Страница 82: ...no content intended for this page 70...
Страница 86: ...no content intended for this page 74...
Страница 98: ...Table 30 Service Record Date Description of Service Performed By 86...
Страница 104: ...no content intended for this page 92...
Страница 106: ...no content intended for this page 94...
Страница 114: ...no content intended for this page 102...
Страница 138: ...no content intended for this page 126...
Страница 140: ...no content intended for this page 128...
Страница 145: ...no content intended for this page 133...