H.6.1 Clearing the totalizer
Batch totals can be controlled through Foundation Fieldbus
(see Figure 136 below). The user can start, stop, or reset
batch totalizers by setting the option on the
TOTALIZER_CMD
function of the
Composite Transducer Block
. To set the
totalizers from the Foundation Fieldbus:
1. Verify that the gate and ground terminals on the Main
PCB are connected.
2. Program the
CALIBR_MODE_SELECTION
parameter on
the
Composite Transducer Block
to
Gate Input
.
After these steps are complete, you can control the batch
totalizer (start, stop, or reset) by selecting the desired option
on
TOTALIZER_CMD
and writing the changes to the meter. No
password is required for this function.
IMPORTANT:
The Inventory Totalizer can only be reset at the factory.
Figure 136: TOTALIZER_CMD function on composite TB
117
Содержание Panametrics PanaFlow LC
Страница 1: ...PanaFlow LC User s manual 910 327 Rev A...
Страница 2: ...ii...
Страница 3: ...PanaFlow LC Panametrics liquid ultrasonic flowmeter User s manual 910 327 Rev A Sep 2019 iii...
Страница 4: ...no content intended for this page iv...
Страница 12: ...no content intended for this page xii...
Страница 44: ...Figure 58 Setting up pulse output 32...
Страница 49: ...Figure 60 Setting up alarm output 37...
Страница 80: ...no content intended for this page 68...
Страница 82: ...no content intended for this page 70...
Страница 86: ...no content intended for this page 74...
Страница 98: ...Table 30 Service Record Date Description of Service Performed By 86...
Страница 104: ...no content intended for this page 92...
Страница 106: ...no content intended for this page 94...
Страница 114: ...no content intended for this page 102...
Страница 138: ...no content intended for this page 126...
Страница 140: ...no content intended for this page 128...
Страница 145: ...no content intended for this page 133...