Certification and Safety Statements
Certification and Safety Statements for PanaFlow PF10 Zx
• When installing this apparatus, the following
requirements must be met:
• Field wiring shall be rated at least 5°C above maximum
ambient or fluid temperature, whichever is greater.
• Connecting cables shall be mounted securely and
protected from mechanical damage, pulling and
twisting.
• Cable entry is ¾” NPT.
• Cable glands of an approved flameproof design are
required. These must be installed according to the
manufacturer’s instructions. Where the cable glands
are provided by Panametrics, the manufacturer’s
instructions, as supplied to Panametrics, will be included
in the documentation.
• Conduit seals are required within 18” of the enclosure
• Cable glands of an approved flameproof design are
required. These must be installed according to the
manufacturer’s instructions. Where the cable glands
are provided by Panametrics, the manufacturer’s
instructions, as supplied, to Panametrics, will be
included in the documentation.
• The system is covered by the certificate numbers
FM13ATEX0070X and IECEx FMG 13.0028X as shown on
the labels below. The system is certified as ATEX and
IECEx: II 2 G Ex d IIB +H2 T6 Gb in Ta = -40°C to +60°C
ambient, Type 4X and IP66. The system temperature
code is dependent upon the process fluid temperature
ranges of -40°C to +150°C. Refer specific conditions of
use for ATEX and US/Canada for more information about
temperature code.
• Unused cable entries must be sealed using a certified
threaded plug.
• Modifications to the flameproof enclosure are not
permitted.
• The apparatus should be de-energized before opening.
• Installation shall be in accordance with the installation
instructions and the National Electrical Code® ANSI/NFPA
70, the Canadian Electrical Code C22.1, or IEC/EN 60079-
14, as applicable.
• Equipment is of type flameproof “d” design and
complies with the standards identified in the table on
page 2.
• The product contains no exposed parts which produce
surface temperature infrared, electromagnetic ionizing,
or non-electrical dangers.
• The product must not be subjected to mechanical or
thermal stresses in excess of more than those permitted
in the certification documentation and the instruction
manual.
• The product cannot be repaired by the user; it must be
replaced by an equivalent certified product. Repairs
should only be carried out by the manufacturer or by an
approved repairer.
• Only trained, competent personnel may install, operate
and maintain the equipment.
• Consult the manufacturer if dimensional information on
the flameproof joints is necessary.
• The product is an electrical apparatus and must be
installed in the hazardous area in accordance with the
requirements of the EU Type Examination Certificate.
The installation must be carried out in accordance with
all the appropriate international, national and local
standard codes and practices and site regulations
for flameproof apparatus and in accordance with the
instructions contained in the manual. Access to the
circuitry must not be made during operation.
• The flameproof joints of the equipment are not intended
to be repaired. Consult the manufacturer if dimensional
information on the flameproof joints is necessary.
• Follow the manufacturer’s instructions to reduce the
potential of an electrostatic charging hazard.
• Consult the manufacturer for genuine replacement
flange fasteners. M10x35 hexagon socket cap screws of
ISO 12.9 DIN912 grade steel (zinc-plated) or better with a
minimum yield strength of 135,000 psi are acceptable
alternatives.
• Consult the manufacturer for genuine replacement
flange fasteners. M10x35 hexagon socket cap screws of
ISO 12.9 DIN912 grade steel (zinc-plated) or better with a
minimum yield strength of 135,000 psi are acceptable
alternatives.
129
Содержание Panametrics PanaFlow LC
Страница 1: ...PanaFlow LC User s manual 910 327 Rev A...
Страница 2: ...ii...
Страница 3: ...PanaFlow LC Panametrics liquid ultrasonic flowmeter User s manual 910 327 Rev A Sep 2019 iii...
Страница 4: ...no content intended for this page iv...
Страница 12: ...no content intended for this page xii...
Страница 44: ...Figure 58 Setting up pulse output 32...
Страница 49: ...Figure 60 Setting up alarm output 37...
Страница 80: ...no content intended for this page 68...
Страница 82: ...no content intended for this page 70...
Страница 86: ...no content intended for this page 74...
Страница 98: ...Table 30 Service Record Date Description of Service Performed By 86...
Страница 104: ...no content intended for this page 92...
Страница 106: ...no content intended for this page 94...
Страница 114: ...no content intended for this page 102...
Страница 138: ...no content intended for this page 126...
Страница 140: ...no content intended for this page 128...
Страница 145: ...no content intended for this page 133...