Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
111
Type
Description
MSP
Manual call point alarm (sprinkler).
MHA
Manual call point alarm (“hausalarm”).
KEYSW
Keyswitch access. Activation enables the Operator access level for the
control panel (no password required). Only one input per control panel
can be configured to use this mode.
To enable or disable a control panel input:
1. Select Field setup from the Main menu.
2. Select Panel I/O configuration.
3. Select Panel inputs, and then select the corresponding input.
4. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Panel output configuration
Configurable options for control panel outputs are shown below.
Table 56: Configurable options for control panel outputs
Option
Description
Type
Configures the output operation mode
Group_n
Configures the output group number
Class
Configures the output wiring configuration (Class A or Class B)
Control
Enables or disables an output
[BLANK]
Output description
UKSB
Configures the output group activation when the UK school bell activates
To configure a control panel output:
1. Select Field setup from the Main menu.
2. Select Panel I/O configuration.
3. Select Panel outputs, and then select the corresponding output.
4. Select the output type.
See Table 57 on page 112 for a list of available output types. The default
setting for all outputs is SND (sounder output).
5. Assign the output to an output group.
See “Output groups” on page 113 for more information on output groups.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......