Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
123
Table 64: Regional investigation time modes
Setting
Description
NO (default)
No investigation mode is required.
MAX_ACK_T
Maximum acknowledgement time.
The configured investigation time starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the investigation time (by
pressing the Panel Silence button), then any sounder or fire routing
delays continue to be processed as configured. If a new zone
reports an alarm after the control panel is silenced, the panel starts
another acknowledgement time period.
If the alarm is not acknowledged during the investigation time (by
pressing the Panel Silence button), then sounders and fire routing
are activated when the configured investigation time elapses.
FREXT_ACK
Extended fire routing delay (typically for Scandinavia).
The configured fire routing delay starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the configured fire routing delay
(by pressing the Panel Silence button), then the extended fire
routing delay becomes the active delay.
If the alarm is not acknowledged during the configured fire routing
delay (by pressing the Panel Silence button), then the extended fire
routing delay is not activated.
FREXT_SND [1]
Extended fire routing delay (typically for Holland).
The standard fire routing delay starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the configured fire routing delay
(by pressing the Sounders Start/Stop button), then the extended fire
routing delay becomes the active delay.
If the alarm is not acknowledged during the configured fire routing
delay (by pressing the Sounders Start/Stop button), then the
extended fire routing delay is not activated.
FREXT_VDS [2]
Extended fire routing delay (typically for Germany).
The configured fire routing delay starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the configured fire routing delay
(by pressing the Investigation Time button), then the extended fire
routing delay becomes the active delay.
If the alarm is not acknowledged during the configured fire routing
delay (by pressing the Investigation Time button), then the extended
fire routing delay is not activated.
[1] Sounder delay must be configured as 0 seconds for this option.
[2] The Investigation Time button is only available on selected models operating in VdS 2540
mode.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......