Chapter 3: Configuration and commissioning
82
ZP2-A Series Installation Manual
Pulse activation
Select Pulse activation to configure the fire routing output activation pulse time, in
milliseconds, for external devices that require pulsed activation. By default the
output activation is continuous.
This option is not available for repeaters or control panels that do not include fire
routing controls.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Pulse Activation.
3. Select and clear the Contin. check box.
4. Select PulseT, and then enter the pulse time value in milliseconds (0 to
10000).
If the PulseT value is 0, the output activation is continuous.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
VdS Settings
Select VdS settings to configure the alarm display format (standard format or
VdS 2540 format).
• Alarms in the standard alarm display format are indicated by zone, loop, and
device (for example, Z0001:D2.018, indicating an alarm in zone 1, loop 2,
device 18).
• Alarms in VdS 2540 alarm display format are indicated by the zone identifier
and the point number of the device in the zone that reports the alarm event
(for example, 0001/18).
By default the standard alarm display format is used (except for control panels
operating in regional mode VdS 2540).
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select VdS settings.
3. Select and clear the Alarms in standard format check box.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......