Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
109
Panel I/O configuration
Panel input configuration
Configurable options for control panel inputs are shown below.
Table 54: Configurable options for control panel inputs
Option
Description
Type
Configures the input operation mode
Control
Enables or disables an input
Input types are shown in Table 55 below. The default mode for all inputs is LG
(logged activation: an unlatched condition stored in the event log).
To configure a control panel input:
1. Select Field setup from the Main menu.
2. Select Panel I/O configuration.
3. Select Panel inputs, and then select the corresponding panel input.
4. Select the input type.
See Table 55 below for a list of available input types.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Table 55: Configurable input types
Type
Description
LG (default)
Logged activation. An unlatched condition that generates no indications
but it is only stored on the event log.
T_AL
Technical alarm activation. A latched condition indicated on the LCD
and stored in the event log.
This input type can be used for gas detectors.
T_ALu
Technical alarm activation. An unlatched condition indicated on the LCD
and stored in the event log.
This input type can be used for gas detectors and for connecting to
aspirating detector Alert outputs.
DT_AL
Disable technical alarm inputs. When active, this input disables all the
technical alarm inputs (latched and unlatched).
DET
Detector alarm.
This input type can be used for connecting to aspirating detector Fire1
outputs.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......