Chapter 3: Configuration and commissioning
64
ZP2-A Series Installation Manual
Viewing or clearing the event log
Select View all or Clear to view or clear alarm, fault, and condition events logged
by the control panel.
To view or clear the event log:
1. Select Reports from the Main menu.
2. Select Event log, and then select View all (to view all current entries) or Clear
(to delete all current entries).
3. Press F2 (Exit) to exit the menu.
The event log can include a maximum of 9,999 entries. When the maximum
number of entries is reached, the oldest entries are deleted as new entries are
recorded.
Backing up the event log
Select Backup to create a backup of the event log. The backup reports are saved
to a USB flash drive (not supplied) in XML format and can be viewed with the
Configuration Utility.
Note:
Use only FAT32 file system USB flash drives with a maximum capacity of
32 GB.
To back up the event log:
1. Open the control panel cabinet door.
2. Insert a USB flash drive into either of the USB connectors (Figure 23, item 1).
3. Close the control panel cabinet door.
4. Select Reports from the Main menu.
5. Select Event log, and then select Backup.
6. Follow the on-screen instructions.
7. Press F2 (Exit) to exit.
8. Remove the flash drive as described in “Removing a USB device” on page
57.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......