Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
93
Ethernet configuration
Select Ethernet configuration to configure settings for monitoring network
communication with the central monitoring station (CMS). Configuration options
are shown in the table below.
Table 38: Ethernet configuration options
Option
Description
Default value
Period
Configures the heartbeat period (in seconds)
3
Fails
Configures the minimum number of consecutive heartbeat
failures required to indicate a communication error with the
central monitoring station
3
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select DACT config, and then select Ethernet config.
3. Select Period, and then enter the value in seconds (1 to 99).
4. Select Fails, and then enter the value (1 to 10).
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Site configuration
Select Site configuration to configure the primary CMS, backup CMS, event
types to report, and event reporting mode for configured central monitoring
stations.
Table 39: Site configuration options
Option
Description
Default value
Primary [1]
Configures the primary CMS (CMS1 to CMS7).
NO
Backup [1]
Configures the backup CMS (CMS1 to CMS7).
NO
Event
Configures the event types to report (see Table 40 below). NO
FR_ERM [2]
Configures the event reporting mode for the corresponding
central monitoring station: Fire Routing mode (for alarm
event transmission) if checked or Event Reporting mode if
not checked.
Event Reporting
mode
[1] In the event of communication problems reporting an event to the primary CMS, the control
panel will send the event notification to the backup CMS.
[2] The global FR_ERM setting in General Configuration takes priority over any individual CMS
setting configured here.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......