Chapter 3: Configuration and commissioning
86
ZP2-A Series Installation Manual
To save a configuration to file:
1. Open the control panel door and insert the USB flash drive into either of the
USB type A connectors (see “Cabinet and PCB layout” on page 19). Close
the control panel door.
2. Select Panel setup from the Main menu.
3. Select Configuration, and then select Save configuration.
The current configuration is saved in XML format using a default naming
format.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
6. Remove the USB flash drive as described in “Removing a USB device” on
page 57.
Restoring the default configuration
Select Default configuration to restore the system to the default factory settings
detailed in Appendix A “Default configurations” on page 149.
Caution:
For large cabinet control panels with an internal 10 A power supply (-P
variants), always confirm that the PSU supervision setting is 10 A after restoring
the system configuration (see “PSU supervision” on page 83).
To restore the default system configuration:
1. Select Panel setup from the Main menu, and then select Configuration.
2. Select Default configuration and confirm your selection.
3. Press F4 (Enter), and then press F1 (Back).
4. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......