Chapter 3: Configuration and commissioning
108
ZP2-A Series Installation Manual
Operating mode
Description
MHA [1]
The zone only allows “hausalarm” manual call points (or inputs
configured for “hausalarm” manual call point operation mode).
Fire routing output groups are not activated in the event of an alarm
in a zone operating in this mode.
[1] The control panel will not allow configuration of zone devices or inputs that do not meet the
corresponding criteria shown in the Description column.
Area configuration
Select Area configuration to configure confirmation areas. An area is a group of
zones where an alarm event can confirm the initial alarm in a zone.
The maximum number of areas available to configure is 256 (all control panels,
regardless of the number of loops).
To configure an area:
1. Select Field setup from the Main menu, and then select Zone configuration.
2. Select Area configuration.
3. Select the area number to configure.
A list of available zones is displayed.
4. Select zones to be included in the confirmation area and press the jog dial to
confirm each selection.
YES indicates that a zone is included in the confirmation area, NO indicates
that a zone is not included in the confirmation area.
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Note:
When configuring a confirmed zone, remember that remote zones with the
same zone number can activate a control panel alarm without confirmation. To
avoid this type of unwanted alarm, configure the remote zones accordingly.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......