Appendix A: Default configurations
150
ZP2-A Series Installation Manual
Description
Default setting
Autosetup zone
Initial zone OpMode configured as Mixed
All detectors, manual call points, and zone modules to the
initial zone
All sounders to output group 1 (sounders)
All relay/non-supervised outputs to output group 301
(program)
All extinguishing modules to output group 801
(extinguishing)
All inputs configured as technical alarm latched
OUT1, OUT2, etc. (Class B)
Sounder output (all zones)
Fire output
Activated by fire alarms in all zones
Fault output
Follows the General Fault LED and is activated when there
is no fault (fail-to-safe)
IN1 and IN2
Logged activation (LG)
Delays
All delays to 0 in all zones
Sounder, fire routing, fire protection, and program groups to
be activated by all zones
Sounders silence disable time 60 seconds
Expansion boards
None