Chapter 3: Configuration and commissioning
118
ZP2-A Series Installation Manual
Activation configuration
Select Activation configuration options to configure the activation delays for
output groups, investigation times, and general sounders behaviour (sounder
silencing and second stage usage).
Note:
This option is not available on repeater panels.
Delay configuration options are shown in the table below.
Table 61: Activation configuration options
Option
Description
Sounders
Configures the activation of sounder groups with zones in alarm. A
warning delay can also be configured if the second stage delay option is
required.
Fire routing
Configures the activation of fire routing groups with zones in alarm.
Fire protection
Configures the activation of fire protection groups with zones in alarm.
Program
Configures the activation of program groups with zones in alarm.
Per zone
Configures the activation of output groups for each individual zone in
alarm. For each zone, a different output group activation delay (including
no activation) can be assigned for each configured output group.
General delays
Configures sounder silence disable time, maximum acknowledge time or
extended fire routing delays, and warning time for second stage sounders
applications.
Sounder, fire routing, fire protection, and program output group delays
Select an output group type to configure delays (including no activation) for
sounder, fire routing, fire protection, and program output groups for all zones.
These output groups can be configured individually or all output group types at
the same time. All zones are programmed with the same setting: global delay or
no activation.
Configurable options for output group delays are shown in the table below.
Table 62: Configurable options for output group delays
Field
Description
Group_n
Output group selection (all output groups of the type selected or a
single output group of the type selected)
Active
Output group activation (yes or no)
Delay
The delay (in minutes and seconds)
Wrn_Dly [1]
The warning delay (in minutes and seconds)
[1] Sounder output group delays only.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......