Chapter 3: Configuration and commissioning
94
ZP2-A Series Installation Manual
Table 40: Site configuration event types
Option
Description
A
Configures alarm reporting
F
Configures fault reporting
C
Configures condition reporting
AF
Configures alarm and fault reporting
AFC
Configures alarm, fault, and condition reporting
FC
Configures fault and condition reporting
AC
Configures alarm and condition reporting
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select DACT config, and then select Site config.
3. Select the site to configure (Site 1 or Site 2).
4. Configure all required settings.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
CMS configuration
Select CMS configuration to configure central monitoring station communication
and account settings. Up to seven monitoring stations can be added – four over
IP and three over PSTN. Configuration options are shown in the table below.
Table 41: CMS configuration options
Option
Description
Default value
IP/Port [1]
Configures the CMS IP address and communication port.
000.000.000.000/
09999
Dial_n [2]
Configures the PSTN telephone number
000000000000000
Enabled
Enables or disables communication with the CMS.
NO
Account
Configures the account information that identifies the
control panel. Maximum 6 digits (hexadecimal). Possible
values: 0 to 9 and B to F.
000000
Receiv.
Configures the four-digit TCP/IP receiver number for the
CMS.
0000
Line
Configures the four-digit TCP/IP line number for the CMS. 0000
Network [1]
Configures the network type.
ETH
[1] Only applies to CMS over IP.
[2] Only applies to CMS over PSTN.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......