Chapter 2: Installation
ZP2-A Series Installation Manual
31
Connections
Recommended cables
Recommended cables for optimal system performance are shown in the table
below.
Table 14: Recommended cables
Cable
Cable requirements
Max. cable length
Mains cable
3 × 1.5 mm
2
N/A
Loop cable
0.13 to 3.31 mm² (12 to 26 AWG) shielded or
unshielded twisted-pair (75
Ω
and 700 nF max.) [1]
3.5 km [2]
Loop cable (900 Series
protocol)
0.13 to 3.31 mm² (12 to 26 AWG) twisted-pair
(52
Ω
and 500 nF max.) [1]
3.5 km [2]
Fire network cable
0.13 to 3.31 mm² (12 to 26 AWG) twisted-pair,
CAT5
1.2 km
Ethernet cable
CAT5, CAT5e, or CAT6
30 m [3]
USB cable
Standard USB cable with A-B connectors
10 m
External printer cable
Accessory cable 2010-2-232-KIT [4]
3 m
[1] 37.5
Ω
per wire (or 26
Ω
per wire for the 900 Series protocol).
[2] Maximum cable length depends on the type of cable used and the loop load.
[3] Connect the control panel to an Ethernet switch installed within 30 m if greater distances are
required.
[4] This kit contains a 3 m cable and the 2010-2-232-IB isolation board required for external
RS-232 device connections.
Other types of cable may be used subject to site-specific electromagnetic
interference (EMI) conditions and installation testing.
Using shielded loop cable
Shielded cable provides more flexibility in solving site-specific EMI problems and
is recommended, subject to following these guidelines:
• Use a multimeter to check that the shield is fully isolated from earth, the loop
positive, and the loop negative lines before connecting the shield to a single
point in the installation. The same isolation must be provided for any other
site wiring and loop cabling should avoid any known sources of EMI at the
site.
• Use the earth studs in the control panel cabinet for termination. See “Cabinet
and PCB layout” on page 19 for the location of the earth studs.
The PCB terminal earthing connections only improve noise immunity in very
specific environmental conditions. In some cases, leaving the earth fully
isolated provides the best protection against EMI.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......