Chapter 3: Configuration and commissioning
70
ZP2-A Series Installation Manual
Regional options
Select Regional options to set the regional operating mode. Available options are
shown in the table below.
Table 26: Regional operating modes
Operating mode
Region
EN 54-2 (default)
European Union
EN 54-2 Evacuation
European Union (Spain)
NBN S 21-100 [1]
European Union (Belgium)
NEN 2535/2575 [2]
European Union (Holland)
VdS 2540 [1]
European Union (Germany)
British Standard [3]
United Kingdom
[1] See the corresponding marketplace manuals for additional installation and operation
instructions for these regional operating modes.
[2] Implements NEN 2535 for fire and repeater panels and NEN 2575 for evacuation panels.
[3] Defaults the panel to UK English.
To change the control panel operation mode:
1. Select Panel setup from the Main menu.
2. Select Regional options.
3. Select the operating mode.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit)
Remember to apply saved settings from the Main menu.