Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
119
To configure the output group delay:
1. Select Field setup from the Main menu, and then select Activation
configuration.
2. Select the output group type to configure (Sounder, Fire routing, etc.).
3. Select Group_n, and then select ALL (to configure common delay settings for
all output groups of the type selected) or select the output group number (to
configure custom delay settings for a single output group of the type
selected).
4. Select Active, and then select YES (to confirm output group activation in case
of an alarm) or NO (to deactivate the output group).
5. Select Delay and enter the required delay in minutes and seconds.
The maximum delay value for sounder, fire routing, and fire protection output
groups is 10 minutes. The maximum delay value for program output groups is
16 minutes and 40 seconds.
6. If required, enter a warning delay (in minutes and seconds) for sounder output
groups in applications using warning tones (second stage sounders).
A warning delay is only observed if the corresponding warning time is also
configured (see “Warning time” on page 124 for more information on this
option). The maximum warning delay value is 10 minutes.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Once a delay has been configured, it must be enabled.
Configured delays are only activated for alarms activated by a detector. Alarms
activated by a manual call point ignore any configured delays.
Configured delays can be enabled or disabled by sensitivity mode programming
(day/night mode), remote equipment by means of a programmed input, or the
user interface delay buttons.
By default, the control panel does not process delays when operating in night
mode. Remember that night mode can be activated by the day/night mode
schedule, the holiday calendar, or by remote equipment. For specific
applications, a delay in night mode can be configured if required. See “Additional
day/night mode settings” on page 55.
Use these options to configure, for example, activation of sounders and fire
routing with 2 minute delay for any zone in alarm in the fire network inside the fire
alarm panel zone range.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......