Chapter 4: Maintenance
136
ZP2-A Series Installation Manual
Fire alarm system maintenance
To ensure correct functioning of your control panel and fire alarm system, and
compliance with all European regulations, the following maintenance checks
should be followed.
Caution:
Ensure that fire routing (where configured) has been disabled or that
the fire brigade has been notified of any planned fire alarm tests.
Quarterly maintenance
Contact your installation or maintenance contractor to carry out a quarterly
inspection of the fire alarm system.
This must test at least one device per zone and verify that the control panel
responds to all fault and alarm events.
The control panel power supply should be checked and the batteries tested using
the “Battery test” menu option (see “Battery test fault indications” on page 137).
Annual maintenance
Contact your installation or maintenance contractor to carry out an annual
inspection of the fire alarm system.
This must test all system devices and verify that the control panel responds to all
fault and alarm events. All electrical connections must be visually inspected to
make sure that they are securely fastened, that they have not been damaged,
and that they are appropriately protected.
Cleaning
Keep the outside and inside of the control panel clean. Carry out periodic
cleaning using a damp cloth for the outside. Do not use products containing
solvents to clean the unit. Do not clean the inside of the cabinet with liquid
products.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......