A6-1
IM 34M6H41-02E 2nd Edition : Aug. 1, 2005-00
A6. Errors and Troubleshooting
We describe here the problems that may occur under each usage environment (when
connected to a display, when connected to a PC, when connected to a modem) and the
corresponding corrective actions.
When Connected to a Display
Table A6.1 Problem Causes and Troubleshooting when Connected to a Display
Symptom Cause
Corrective
Action
Equipment number is valid.
Equipment number is zero.
Set to valid equipment number.
(See A1.6, “Connecting to a
Display”)
Communications parameters (communication
speed, ending character Yes/No) of the display
do not match that of the module
Make the communications
parameters (communications
speed, ending character Yes/No)
the same
02: FE error occurs
RS-232-C cable is incorrect.
Pins 7, 8 are not looped back.
Use a cross cable.
Check that pins 7, 8 are connected.
02-51 error occurs
A command from the Personal Computer Link
module to the CPU module has timed out.
Set the number of retries on the
display
02-52 error occurs
Processing error has occurred in CPU module.
An attempt is made to display a device not
supported by the CPU module.
Set the value to data within the
device range of the CPU module.
Other error code
occurs
Refer to the manual of the display device.
Backlight has reached the end of its service life. Replace the backlight.
Screen data is not transferred.
Transfer screen data.
Nothing is displayed on
the screen .
(complete darkness)
The number on the initial screen is invalid.
Set the number of the initial screen
correctly.
*:
The above error codes apply only to the TOP series display. (They are displayed on the last line of the display).
When Connected to a PC
Table A6.2 Problem Causes and Troubleshooting when Connected to a PC
Symptom Cause
Corrective
Action
RS-232-C cable is incorrect.
Pins 7, 8 are not looped back.
Use a cross cable.
Check that pins 7, 8 are connected.
Communications parameters (communication
speed, ending character Yes/No) of the PC do
not match that of the module
Make the communication
parameters (communication speed,
ending character Yes/No) the same
No response is
returned.
The STX and station number in the command is
invalid.
Append a valid STX and station
number.
(station number should be “01”)
An error response
is returned.
Rectify the problem according to the error code table.
The transmission data count specified is
incorrect or zero.
Write the correct transmission data
count (in bytes) into data position
number 101/401.
The event is not
transmitted.
Request to Transmit relay is not turned on.
In a multi-CPU configuration, set up
so that no other CPU is using the
relay.
*:
If a protocol analyzer is available, connect it between the PC and the module to observe the commands and
responses flowing to-and-fro.
Summary of Contents for F3LC11-1F
Page 2: ......
Page 12: ...Blank Page...
Page 48: ...Blank Page...
Page 65: ...A3 7 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 430 PR CLOSE 440 450 FIN 460 470 END...
Page 74: ...Blank Page...
Page 82: ...Blank Page...
Page 92: ...Blank Page...
Page 94: ...Blank Page...
Page 120: ...Blank Page...
Page 136: ...B3 6 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 450 460 END...
Page 140: ...Blank Page...
Page 142: ...Blank Page...
Page 146: ...Blank Page...
Page 148: ...Blank Page...
Page 168: ...Blank Page...
Page 176: ...Blank Page...
Page 200: ...Blank Page...
Page 202: ...Blank Page...