C6-2
IM 34M6H41-01E
3rd Edition : Aug. 1, 2005-00
C6.1 Troubleshooting Flowchart When ‘RDY’ LED Is
Not On
‘RDY’ LED is not on.
YES
NO
YES
Replace this module.
End
YES
Does the power
supply module have the
stipulated voltage?
NO
Is the ‘RDY’ LED
of power supply
module on?
YES
YES
NO
NO
Is any other module
in RDY status?
YES
NO
Is it properly installed
in the slot?
YES
NO
Is the
‘RDY’ LED still
off even when the module is
installed in another
slot?
Replace the power supply
module.
Replace the base module.
Is the ‘RDY’ LED on?
Supply the stipulated voltage.
FC0601.EPS
Replace power supply
module or base module.
Push the module in the slot
until a ‘click’ sound is heard
(refer to Sections C2.1.3 and
C3.1.3 in this manual).