(1) Transmission Speed Switch (SW1)
Set the transmission speed using the hexadecimal rotary switch shown below. With an
appropriate ordinary screwdriver, change the direction of the arrow. Do not position the
arrow at D, E or F. The factory default setting of the switch is C (115.2 Kbps).
SW1 setting
Transmission
speed (bps)
Remarks
0 300
1 600
2 1200
3 2400
4 4800
5 9600
6
14400
See note below
7
19200
See note below
8 28800
9 38400
A 57.6K
B 76.8K
C 115.2K
Factory
setting
D to F
------
Cannot be set
For F3LC12-1F, the switch setting applies to both port 1 and port 2.
Use software setup to change the setting for individual ports.
Note: On F3LC11-1N, switch setting 6 represents 19200 bps.
However, on F3LC11-1Fand F3LC12-1F, switch setting 7 represents 19200 bps.
(SW setting 6 represents 14400 bps)
Figure A1.3 Transmission Speed Switch of Personal Computer Link Module
(F3LC11-1F/F3LC12-1F)
(2) Data Format Switch (SW2)
Set the data transmission format using the 8-bit DIP switch. Set the DIP switch by
sliding each switch to the ON or OFF position. Up to six functions can be set with this
switch. The factory setting is ON for bit 1 and OFF for bits 2-8.
1
2
3
4
5
6
7
8
O
F
F
Number
(SW2)
Function OFF
ON
Factory
setting
1
Character length
7 bits
8 bits
8 bits
ON
2 None
Yes
None
OFF
3
Parity
Odd Even
---- OFF
4
Stop bit
1 bit
2 bits
1 bit
OFF
5 Checksum None
Yes
None
OFF
6 Ending
character
None
Yes
None
OFF
7 Protection
feature
None
Yes
None
OFF
8 Security
feature
None
Yes
----
OFF
-
For F3LC12-1F, the SW setting applies to both port1 and port 2.
-
To change the setting for an individual port, use software setting.
-
SW2-3 is valid only if parity s enabled (SW2-2 is on).
-
When connecting to a modem, use the following setting: “8 bits SW2-1=ON, No parity
SW2-2=OFF” or “7 bits SW2-1=OFF, with parity SW2-2=ON”
FA10407.VSD
Figure A1.4 Data Format Switch of Personal Computer Link Module (F3LC11-1F/F3LC12-1F)
Summary of Contents for F3LC11-1F
Page 2: ......
Page 12: ...Blank Page...
Page 48: ...Blank Page...
Page 65: ...A3 7 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 430 PR CLOSE 440 450 FIN 460 470 END...
Page 74: ...Blank Page...
Page 82: ...Blank Page...
Page 92: ...Blank Page...
Page 94: ...Blank Page...
Page 120: ...Blank Page...
Page 136: ...B3 6 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 450 460 END...
Page 140: ...Blank Page...
Page 142: ...Blank Page...
Page 146: ...Blank Page...
Page 148: ...Blank Page...
Page 168: ...Blank Page...
Page 176: ...Blank Page...
Page 200: ...Blank Page...
Page 202: ...Blank Page...