Error Code in Response
A communication error may occur while receiving a command. In this case, this module
replies with ER (character string) and an error code.
The following error codes are provided.
Table C4.1 Error Codes in Response
T0401.EPS
Error
code
(EC1)
Semantics
Probable causes
FA-M3 (F3LC11-1N and F3LC11-2N)
• CPU number is out of the valid range of 1 to 4.
• Command does not exist.
• Command is not executable.
• Device name does not exist. (See Table C4.2, “Detailed Error Codes.”)
• The specification is not correct when a bit device is used in words.
• Characters other than 0 and 1 are used for bit setting. Refer to Table C4.2,
“Detailed Error Code.”
• word setting is out of the valid range of 0000 to FFFF.
• Start position exceeds the address range in Load/Save, etc.
• Specified bit count, word count, etc. exceeds the specification range (see Table
C4.2, “Detailed Error Code.”)
• The specified data count and the device parameter count, etc. do not match.
• Monitor is operated without monitor specification (BRS, WRS)
• A parameter other than those mentioned above is invalid.
• Error has occurred during communication (see Table C4.2, “Detailed Error Codes.”)
• Value of checksum differs. (Bit omitted or changed characters)
• Data received exceeds stipulated value.
• Ending character or ETX was not received.
• Timeout duration is 5 seconds.
• Sequence CPU hardware failure
• Sequence CPU command reception disabled
This failure may occur temporarily in the following cases:
• Immediately after supplying power to a sequence CPU with a 9 K-step or
longer program,
• Immediately after downloading a 9 K-step or longer program to the CPU, or
• Immediately after online editing of a 9 K-step or longer program.
Corrective action: Re-send commands.
• Insufficient sequence CPU service time
This may occur if the Ladder Diagram Programming Tool M3 is used and more than
20 READ/WRITE/DREF instructions are executed each scan.
Corrective action: • Reduce the number of READ/ WRITE/DREF instructions
executed in each scan or
• specify constant scan.
If detailed error code E1 is added, consult Table C4.2.
• CPU has detected an error during processing.
• Error has occurred in internal processing.
01
CPU number error
02
Command error
03
Device specification
error
04
Value outside the
setting range
05
Data count out of
range
06
Monitor error
08
Parameter error
41
Communication error
42
Checksum error
43
Internal buffer overflow
44
Timeout while
receiving characters
51
Timeout error (5
seconds)
CPU communications
error
52
CPU processing error
F1
Internal error
Summary of Contents for F3LC11-1F
Page 2: ......
Page 12: ...Blank Page...
Page 48: ...Blank Page...
Page 65: ...A3 7 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 430 PR CLOSE 440 450 FIN 460 470 END...
Page 74: ...Blank Page...
Page 82: ...Blank Page...
Page 92: ...Blank Page...
Page 94: ...Blank Page...
Page 120: ...Blank Page...
Page 136: ...B3 6 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 450 460 END...
Page 140: ...Blank Page...
Page 142: ...Blank Page...
Page 146: ...Blank Page...
Page 148: ...Blank Page...
Page 168: ...Blank Page...
Page 176: ...Blank Page...
Page 200: ...Blank Page...
Page 202: ...Blank Page...