![YOKOGAWA F3LC11-1F User Manual Download Page 69](http://html1.mh-extra.com/html/yokogawa/f3lc11-1f/f3lc11-1f_user-manual_3448059069.webp)
A3-11
IM 34M6H41-02E 2nd Edition : Aug. 1, 2005-00
240
:! Setup telephone number
250 CONTROL LCSLOT,29;10
:! Telephone number size
260 CONTROL LCSLOT,30;1
:! No. of dial digits for ext. connection
270 CONTROL LCSLOT,31;$9012
:! Telephone number
280 CONTROL LCSLOT,32;$3456
290 CONTROL LCSLOT,33;$7890
300 !
310 MAIN@
320 GOSUB SDMSGPB@
330 IF RSLT=0 THEN PR "SEND OK" ELSE PR "SEND NG" ENDIF
340 STOP
350 !
360 SDMSGPB@
370 RSLT=0
380 !
390 CONTROL LCSLOT,101;$0000,$07F6
:! Turn off output relay
400 !
410 STATUS LCSLOT,101;XREL
:! Read input relay
420 IF BIT(XREL,8)=1 THEN FINER@
:! Check for external connection
430 !
440 CONTROL LCSLOT,101;$0040,$0040
:! Turn on Y39
(Transmit to Beeper)
relay
450 CONTROL LCSLOT,101;$0080,$0080
:! Turn on Y40
(Dial Request)
relay
460 STATUS LCSLOT,101;XREL
:! Read input relay
470 WHILE BINAND(XREL,$00B0)=0
:! Wait till X5(Connected)
relay turns on
480
:! or X6 (Connection Failed)
turns on
490
:! or X8 (Disconnection Failed) turns on
500 STATUS LCSLOT,101;XREL
:! Read input relay
510 END WHILE
520 CONTROL LCSLOT,101;$0000,$0080
:! Turn off Y40
(Dial Request)
relay
530 IF BIT(XREL,2)=1 THEN FINER@
:! Skip if connection fails
540 PR "CONNECT"
550 !
560 CONTROL LCSLOT,101;$0002,$0002
:! Turn on Y34
(Request to Send)
relay
570 STATUS LCSLOT,101;XREL
:! Read input relay
580 WHILE BIT(XREL,1)=0
:! Wait until X2
(Transmit Completed)
relay turns on
590 STATUS LCSLOT,101;XREL
:! Read input relay
600 END WHILE
610 CONTROL LCSLOT,101;$0000,$0002
:! Turn off Y34
(Request to Send)
relay
620 PR "SEND MESSAGE"
630 !
640 WAIT 4000
:! Wait before disconnecting line
650 !
660 CONTROL LCSLOT,101;$0400,$0400
:! Turn on Y43
(Disconnect Line)
relay
670 STATUS LCSLOT,101;XREL
:! Read input relay
680 WHILE BIT(XREL,4)=1 AND BIT(XREL,7)=0
:! Wait until X5
(Connected)
relay is off or
690
:!
X8
(Disconnection Failed)
relay is on
700 STATUS LCSLOT,101;XREL
:! Read input relay
710 END WHILE
720 CONTROL LCSLOT,101;$0000,$0400
:! Turn off Y43
(Disconnect Line)
relay
730 !
Summary of Contents for F3LC11-1F
Page 2: ......
Page 12: ...Blank Page...
Page 48: ...Blank Page...
Page 65: ...A3 7 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 430 PR CLOSE 440 450 FIN 460 470 END...
Page 74: ...Blank Page...
Page 82: ...Blank Page...
Page 92: ...Blank Page...
Page 94: ...Blank Page...
Page 120: ...Blank Page...
Page 136: ...B3 6 IM 34M6H41 02E 2nd Edition Aug 1 2005 00 450 460 END...
Page 140: ...Blank Page...
Page 142: ...Blank Page...
Page 146: ...Blank Page...
Page 148: ...Blank Page...
Page 168: ...Blank Page...
Page 176: ...Blank Page...
Page 200: ...Blank Page...
Page 202: ...Blank Page...