6.2 Startup Sequence and Basic Operation
6-3
6
6.2 Startup Sequence and Basic Operation
This section explains the startup sequence and basic operation of the MP2100/MP2100M. The methods for
setting the mode switch, the types of self-diagnosis, and the indicator patterns are also explained.
6.2.1 MP2100 Mode Switch Settings
The mode switch is used to control the startup sequence for the MP2100. The following table shows the function
of each switch.
(1) Mode Switch 1 (S1)
(2) Mode Switch 2 (S2)
* Set the CP number allocated to the communication process logic port. When using two or more
MP2100s, set different CP number.
Mode Switch 1 (S1)
Mode Switch 2 (S2)
1
2
ON
2
3
4
5
6
1
No.
Name
Status
Function
Factory
Setting
Details
1
INIT
ON
Memory Clear
OFF
Set to ON to clear memory. If this switch is set
to OFF, the program stored in flash memory will
be executed.
OFF
Normal operation
2
STOP
ON
User program stopped
OFF
Stops the user program execution. Enabled only
when the power is turned ON.
OFF
User program running
No.
Name
Status
Function
Factory
Setting
Details
1
TEST
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
2
MON
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
3
CNFG
ON
Configuration mode
OFF
Set to ON to execute self-configuration for
connect devices.
OFF
Normal operation
4
SUP
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
5
SLOT0
SLOT1
ON
ON
OFF
OFF
- SLOT0
- ON
- OFF
- ON
- OFF
CP4
CP3
CP2
CP1
OFF
Use to set CP number.
∗
6
SLOT1
OFF