5009 Installation/Hardware
Manual 85580V2
iv
Woodward
Regulatory Compliance
Unless otherwise specified, this equipment is suitable for use in Class I, Division
2, Groups A, B, C, and D or non-hazardous locations only.
Suitability for installation of this equipment for installation in Class I, Division 2,
Group A, B, C, D hazardous locations is indicated by the presence of a third
party safety agency logo along with the hazardous area classification affixed to
the equipment model to which it pertains. Absence of a hazardous area
classification indicates the equipment is only to be installed or used in ordinary
(non-hazardous) locations.
Relay modules—such as Discrete Termination Modules (F/T Relay–Discrete
In)—are NOT suitable for use in hazardous locations and must be located in a
non- hazardous area or use a suitable method of protection approved by the
local safety authority.
Wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction. UL approved branch circuit protection
not exceeding 250% of rated full load input current for the 5009 main power supply
must be provided and must be acceptable for the applicable area classification.
WARNING—EXPLOSION HAZARD
This equipment is not suitable for use in Class I, Division 2 hazardous
locations if an F/T Relay module is installed in the cabinet. It is to be used in
Ordinary or non-hazardous locations only.
Substitution of components may impair suitability for Class I, Division 2.
Do not remove or install power supply, modules, or other equipment while
the circuit is live unless area is known to be non-hazardous.
Do not connect or disconnect equipment while circuit is live, unless area is
known to be non-hazardous.
AVERTISSEMENT—RISQUE D’EXPLOSION
La substitution de composants peut rendre ce matériel inacceptable pour
les emplacements de Classe I, Division 2.
Ne pas enlever ni installer l’alimentation électrique, les cartes, ou d’autre
équipement pendant que le circuit est sous tension avant de s’assurer que
la zone est non dangereuse.
Ne pas raccorder ni débrancher tant que l’installation est sous tension, sauf
en cas l’ambiance est décidément non dangereux.
WARNING—PROPER USE
If the equipment is used or applied in a manner not specified here-in, the
protection provided by the equipment may be impaired.
WARNING—HIGH VOLTAGE
If 125 Vdc is present on the DTM terminal blocks, there will be 125 Vdc on
the discrete module cables. If power cannot be removed from the DTM,
extreme care must be taken to avoid contact with the cables.
CAUTION—MAXIMUM VOLTAGE
To comply with CE Marking under the European Low Voltage Directive
(LVD), the maximum external circuit voltage for both the Discrete Inputs and
Relay Output circuit are limited to 18–32 Vdc maximum.
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......