5009 Installation/Hardware
Manual 85580V2
86
Woodward
Chapter 6.
Hardware Specifications
5009 Control Package—Not Including Optional Hardware
(except as noted)
Safety and EMC Standards Compliance
•
Conforms to EMC Directive 89/336/EEC. Conformity established by test to
EN 61000-6-2 and EN 61000-6-4.
•
Conforms to Low Voltage Directive 73/23/EEC when used in accordance
with instructions. Conformity established by testing to EN50178 1997.
•
Listed UL and cUL Industrial Control Equipment for Class I, Division 2,
Groups A, B, C, and D hazardous locations (MicroNet TMR
®
/5009 Main
Chassis and Power Supply Chassis with modules. Includes FTMs except FT
Relay module). FT Relay module is Listed UL and cUL Industrial Control
Equipment for ordinary (non-hazardous) locations.
•
Certified by Lloyd’s for ENV1 and ENV2.
Environmental
Humidity
Lloyd’s type ENV2 Humidity test #1: Two temperature cycles between 20 to 55
°C at 95% Relative humidity within 48 hours
Shock
US MIL-STD-810C, Method 516.2-1 procedure 1b (15g 11ms Half Sine pulse)
Vibration
Lloyd’s type ENV2 Vibration test #1
13–150 Hz @ 1.0 G Ten sweeps at one octave per minute
Unless otherwise reduced by options as shown in the Environmental
Classifications for Options Table below, the following classifications apply.
EN 50178
Temp. Class
for Cabinet
EN 50178
Humidity Class
EN 50178
Air Pressure
Class
3K3
5 to 40 °C
3K3
5% to 85%
3K3
86 to 106 kPa
Tested operating temperature range is 0 to 55 °C.
Environmental Classifications for Options
For systems with the optional Cabinet, the presence of any of the following options
reduces the Environmental Class of the cabinet assembly to the lowest classification of
the options present.
Woodward
Part No.
Description
Mfg./Part No.
Mfg. Temp.
Rating (°C)
Cabinet Max.
Ambient (°C)
1790-3000
OpView 90–250 Vac
(color)
PS-10-2T2-DD1-BD5 0–50
0–40
1790-3001
OpView 90–250 Vac
(monochrome)
PS-10-2M2-DD1-BD5
0–50 0–40
N/A No
OpView
N/A N/A 45
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......