5009 Installation/Hardware
Manual 85580V2
90
Woodward
Actuator Driver Outputs
Number of channels:
2
Driver:
Pulse Width Modulated (proportional only), Single or
Dual Coil
PWM frequency:
4.88 kHz
Filtering:
three 500 ms poles
Default output Ranges: 4–20 mA or 20-160 mA, software selectable
Maximum
Current
Range:
2–24 mA or 10–196 mA
Isolation:
Channel to Channel
0 Vrms
To Chassis
200 Vdc continuous, 600 Vdc DWV
Max. act resistance:
45
Ω
on the 20–160 mA output, 360
Ω
on the 4–20 mA
output
Readback:
Actuator source and return currents
Dither current:
25 Hz, fixed duty cycle, software variable amplitude
Resolution:
10
bits
Accuracy:
software calibrated to 0.2%
Temperature Drift:
125 ppm/°C, maximum
Readback accuracy:
0.1%
Readback temp drift:
150 ppm/°C, worst case
Discrete Inputs
NOTE
The F/T Relay Discrete In Panel is suitable for use in non-hazardous
locations only.
Number of channels:
24
Input
type:
Optically
isolated discrete input
Input Thresholds:
< 8 Vdc = “OFF”, > 16 Vdc = “ON”
Input Current:
13 mA @ 24 Vdc
External
Input
Voltages:
18–32 Vdc (meets CE & UL) or 100–150 Vdc (meets UL
only)
Isolation:
Channel to Channel
1100 Vdc
To Control Common
1100 Vdc
To Chassis
500 Vdc continuous
Time stamping:
1 ms resolution
Isolated 24 Vdc supply may be used to power contacts, 400 mA maximum
Relay Outputs
NOTE
The F/T Relay Discrete In Panel is suitable for use in non-hazardous
locations only.
Number of channels:
12
Relay Type:
Dust-tight with magnetic blow-out
Coil Rating:
52 mA @ 24 Vdc
Operating Time:
20 ms max.
Release Time:
10 ms max.
Shock:
5G for 11 ms
Temperature:
–45 to +70 °C
Dielectric Strength:
500 Vrms across open contacts
2500 Vrms between all other conductive elements
Expected Life:
100 000 operations @ rated load
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......