5009 Installation/Hardware
Manual 85580V2
78
Woodward
2. Locate and replace faulty relay (See Figure 4-13). See Chapter 6 of the
manual for recommended replacement relays.
3. Perform a system Reset to clear Alarm.
Diagnostics
Each CPU performs both off-Line and on-line diagnostics. Off-Line diagnostics
are performed at power-up or when the CPU’s Reset switch is toggled. On-Line
diagnostics are performed when the CPU is in its normal operational mode,
under application-program control.
Off-Line Diagnostics
The following list shows the tests run by Off-Line diagnostics, and the order in
which they are run. Off-Line diagnostics are started immediately after a CPU
Reset switch is toggled. If during a diagnostics routine, a particular test fails,
testing is stopped and the failure annunciated, through the Fault LED and
engineering workstation. If an engineering workstation is not connected to the
control at that time the failure is stored for later reading. When a fault is detected
by a diagnostics routine, the CPU module’s Fault LED will periodically repeat
bursts of flashes; the number of flashes in each burst indicates the test that
failed. If the CPU module’s Fault LED flashes replace the module.
Table 5-1. Off-Line Diagnostic Messages
Flashes In Burst
Error Detected
1
Start Up test failed
2
Control Status Register test failed
3
DUART test failed
4
Local RAM test failed
5
Local RAM Misaligned test failed
6
Flash Memory test failed
7
Clock Interrupt test failed
8
VME Bus Timeout test failed
9
EEPROM test failed
10
Floating Point Math Co-processor test failed
11 Real-Time
Clock
failed
On-Line Diagnostics
As soon as the application program starts running, the system will use a small
portion of run time to continuously run on-line diagnostic tests. A failure of any
one of the on-line tests results in the I/O lock being asserted and display of a
message in the PCI’s OpSys Fault mode, as shown in Table 5-2. If the CPU
module’s I/O Lock LED stays on during normal operation replace the module.
Table 5-2. On-Line Test Failure Messages
Local Ram Failed
Checksum Error
Application Ram Failed
System Error (#)
FPU Co-Processor Failed
EEPROM Fault
Task Overrun
Math Exception
Rate Group Slip (#)
EEPROM Initialization Fault
Exception Error Vector #
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......