5009 Installation/Hardware
Manual 85580V2
94
Woodward
Operator Control Panel (OCP)
(8236-341, 8236-361)
The Operator Control Panel includes functions typically used to start and stop a
turbine, and perform overspeed tests. The OCP includes a front access NEMA 4
enclosure and is provided with the switches and meter mounted within the
station’s front door. The Operator Control Station is suitable for use in Class I,
Division 2, Groups A, B, C, and D or non-hazardous locations only. Refer to
Chapter 1 of this volume for related installation and wiring warnings.
To complete the interface to the control, the OCP switches and meter must be
hardwired to the 5009 control and the control program configured to accept the
interface logic (Analog Output and Contact Inputs programmed).
Depending on the station’s purpose, not all the OCP switches may need to be
connected to the control (overspeed, etc.).
Wiring Notes:
Refer to Figure 8-3 for OCP wiring.
•
Wiring must be in accordance with Class I, Division 2 wiring methods and/or
in accordance with the authority having jurisdiction.
•
It is recommended that 0.75 mm² (20 AWG) or larger wire be used between
each device and termination module.
•
Shields should be connected to earth ground at all intermediate terminal
blocks, as well as terminated at the control terminal block. The exposed wire
length, beyond the shield, should be limited to 25 mm (1 inch).
•
Do not place shielded wires in the same cable conduit with high-voltage or
large-current-carrying cables.
Installation of the Operator Control Panel
Mount the control within 300 m (1000 ft) from the 5009 control, leaving an
adequate service loop.
1. Mark the panel location and mounting holes (see Figure 8-2).
2. Drill and tap the mounting holes using the appropriate size hardware.
3. Place the panel in position, insert the mounting screws into the tapped holes,
and tighten the hardware securely.
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......