5009 Installation/Hardware
Manual 85580V2
10
Woodward
Discrete I/O Module (A4)
Each Discrete input/output (I/O) module receives status information from 24
discrete inputs, controls 12 relay outputs and provides latent fault detection for
each relay output. Field wiring is isolated from the 5009 circuitry through optical
isolators on each input channel, and relays on each output channel.
Figure 2-7 is a diagram of the Discrete I/O module. Each CPU sends and
receives information to and from its respective Discrete I/O module via the VME
bus. Each input status is stored in a register and addressed by the CPU as
required. Output commands are driven by the CPU to the Discrete I/O module’s
associated output latches. These latches control the state of output drivers to
energize and de-energize relays. Output Relays are located on the Discrete
Termination Modules.
Each output channel has a readback buffer that stores and indicates the status of
the output driver and associated relays. The CPU compares this status to the
value written to the channel and generates a fault signal if these values are
different.
Figure 2-7. Discrete Input/Output Module
Discrete Termination Modules (F/T Relay Module)
Discrete Termination Modules (DTMs) mount external to the 5009 chassis on a
panel or in a cabinet. The discrete termination modules are used to connect
discrete field wiring to the 5009 control. Four DTMs are provided and used with
each 5009 control. Refer to Figure 4-19 for an overview of modules and DTMs
used. Each DTM connects to the control’s three independent Discrete I/O
modules through individual cables, and provides a common cage-clamp terminal
connection for customer field wiring. A DTM contains circuitry for six contact
inputs, three relay outputs and houses circuitry to:
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......