Manual 85580V2
5009 Installation/Hardware
Woodward
47
When a relay output is open, the contacts of all six relays are open. Because of
the series-parallel configuration that the relays are in, the failure of any one relay
will not cause the output to be closed. The relay output would continue to be
open. Once a relay output is open, the output’s individual relays are periodically
closed and re-opened one by one, to ensure that they were in the correct state,
and that they change state. Position readback circuitry allows the state of each
relay contact to be detected. Any failures are annunciated, and further testing is
disabled without affecting the state of the relay output contact or control
operation.
Latent fault detection (LFD) is not usable with all applications or circuits. The
control’s LFD logic can only work with circuits using voltages between 18–32
Vdc, 100–150 Vdc, or 88–132 Vac. For LFD to work, a small leakage current is
passed through the circuit’s load. See Figure 4-15. Depending on the size of the
load, the leakage current may be enough to cause a load to be on or active,
when a relay contact is open. In this case, the individual relay’s LFD logic may be
disabled, eliminating the leakage current.
If LFD is desired, but the leakage current is too great for the load, an external
resistor may be connected in parallel with the circuit’s load to shunt some of the
leakage current away from the load. To prevent failure of a load to de-energize,
careful consideration should be given, to ensure that the voltage developed
across the load due to leakage current is below the load’s drop-out voltage.
With LFD, when a relay contact is closed, no difference in operation is
experienced; the relay output appears as a closed contact. However, when a
relay contact is open, it appears to the interfaced circuit as a large resistor
instead of an open contact. Thus a small amount of current is leaked to the load,
resulting in a developed voltage across the load. In most cases this has no
bearing on the customer’s circuitry, because such a small amount of voltage is
developed across its load. However, when a relay output is used with a very high
resistance load (low current load), enough voltage may be developed across the
load to prevent it from de-energizing.
To verify if Latent Fault Detection can be used with a relay output:
1. Verify that circuit the relay output is used with has a voltage level of 18–32
Vdc, 100–150 Vdc, or 88–132 Vac. If circuit voltage is not within these
ranges, disable the relay output’s latent fault detection by placing the relay
jumpers in their disable state. See Figure 4-13.
2. Use the graph below (Figures 4-10, 4-11, or 4-12) which corresponds to the
circuit’s voltage level to determine if the voltage developed across the load
(due to the leakage current) is lower than the load’s drop-out voltage level.
•
Acquire the resistance of the load (relay, motor, solenoid, etc.) to be
driven by the relay.
•
Acquire the load’s minimum drop-out voltage.
•
From the bottom of the graph, follow the line corresponding to the load’s
resistance, up until it intersects the circuit power line. At this point the
corresponding voltage level (on the left of the graph) is the level of
voltage that will be developed across the load due to leakage current.
3. If the developed load voltage (from the graph) is less than the load’s drop-out
voltage, latent fault detection can be used with the circuit.
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......