Manual 85580V2
5009 Installation/Hardware
Woodward
43
Figure 4-7. Example Dual Coil Actuator Wiring Diagram
DTM Contact Inputs (F/T Relay–Discrete In)
The 5009 control accepts 24 contact inputs. Each of the control’s four Discrete
Termination Modules accept six contact inputs. Of the 24 contact inputs
available, four have functions already assigned to them (preset) and cannot be
changed, the other 20 are user-configurable. The Preset Contact Inputs are:
•
External Emergency Shutdown
•
External Reset
•
Raise Speed Setpoint
•
Lower Speed Setpoint
The control will initiate an emergency shutdown any time the External
Emergency Shutdown contact input is opened. This input is typically tied into the
system’s trip string. Before starting, the External Emergency Shutdown input
must have an external contact or switch wired to it and it must be closed. The
external reset contact can be used to remotely clear latched alarms and trip
conditions. The raise and lower speed setpoint inputs can be used to remotely
raise and lower speed or load.
Applications requiring external contact inputs must have the desired function
assigned or configured to a specific input. Refer to Volume 3 of this manual for a
complete list of programmable contact input options. If the 5009 control is
configured for a generator application two of the contacts must be configured for
the Generator and Utility breaker inputs. The Generator Breaker contact must be
wired so it is closed when the generator breaker is closed. The Utility Tie Breaker
contact must be wired so it is closed when the utility tie breaker is closed.
Contacts must change state for a maximum of 40 milliseconds and a minimum of
20 milliseconds for the control to sense and register a change in state.
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......