Optionally a line printer can be utilized with the 5009 control to print alarms as
they occur, and upon command, the system’s last 100 Alarms, or the systems
last 20 trips. The CPU-B port or an SIO module’s Port 1 are the only ports which
have the capability to interface with a line printer. Before the CPU-B port will
correctly function with a serial printer it must be configured for this function
through the control’s PCI engineering workstation. Refer to Volume #3 of this
manual for information on configuring the CPU-B port, and printing alarm and trip
lists.
See Figure 4-29 for a diagram of the required printer communications cable. If an
OpView™ operator interface is provided with the system, optionally a line printer
can connected to the OpView for alarm documentation. See Volume #4 of this
manual for information on connecting a line printer to the OpView operator
interface.
OpView
If provided with a cabinet, the OpView, its communications cable, and a power
cable will be factory installed. With the cabinet mounted option the OpView is
installed in the cabinet front door with an RS-232 communications cable
connected between the OpView’s Com-2 Port and the control’s SIO J3 port. For
ease of installation, a power cable is connected from the OpView to the cabinet’s
power panel terminals. This allows a customer to make all system power
connections through one panel. See Figure 4-27.
The OpView can communicate via RS-232, RS-422, or RS-485 communications.
RS-232 communications is limited to 15 m (50 ft) or less. However with the use
of an RS-232 to RS-422 converter or Woodward’s SIO module, the OpView can
be installed up to 1220 m (4000 ft) from the control (see Volume 4 of this
manual).
Optionally a line printer can connected to the OpView operator interface for alarm
documentation. See Volume 4 of this manual for information on connecting a line
printer to the OpView operator interface.
If a cabinet is not supplied with the system, the OpView must be mechanically
installed before electrical installation can be performed. Follow the below wiring
notes to electrically install the OpView.
Wiring Notes (when provided without a cabinet):
•
Reference the PowerStation manual included, for general installation
procedures.
•
Refer to Figures 4-27 and 4-28 for OpView wiring.
•
Connect input power to the OpView’s power connector. Refer to Chapter 6
of this manual for input power requirements.
•
Connect “W21” communications cable between the control’s designated
port and the OpView’s Com2 port. If desired a longer cable can be created
and used between the control and OpView.
Summary of Contents for MicroNet TMR 5009
Page 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Page 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Page 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Page 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Page 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Page 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Page 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Page 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Page 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Page 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Page 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Page 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Page 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Page 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Page 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Page 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Page 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Page 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Page 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Page 115: ......
Page 116: ...Declarations...
Page 117: ......