Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
119
of
196
Unit Mode = BST Client
Unit Mode = BST Manager
Figure 6.3.1-2: BST Cascade: Cascade Configuration Screen
3. Additional parameters now appear, depending on which
Application
is currently chosen in
. Note, the
Application
in that section can be
set to
SH
,
DHW
or
Other
, or any of the combination Applications that includes
SH
,
DHW
or
Other
. For example, if
Application
SH+DHW-1-Vlv
(which includes both
SH
and
DHW
) is
chosen in the BST Application Configuration screen, the parameters in both the
SH
and
DHW
columns below will appear.
Consult the table below to determine which parameters apply to your unit; descriptions of
each item appear below the table.
TABLE 6.3: Cascade Configuration Parameters
Parameters
Current BST Application
SH
DHW Other
SH DHW Other
BST Client
BST Manager
1 Auto-Manager Transfer
✓
✓
✓
1a Auto Failover Type (Item 1 = Enabled)
✓
✓
✓
1b Auto-Manager Timer (Item 1 = Enabled)
✓
✓
✓
1c Auto-Manager Addr (Item 1 = Enabled)
✓
✓
✓
1d Backup Manager Addr (Item 1 = Enabled)
✓
✓
✓
2
Hdr Temp Sensor
✓
✓
2a SH Hdr Temp Point (Item 2 = Network, BAS)
✓
✓
2b SH Sensor Comm Addr (Item 2 or 5 = Network or BAS)
✓
✓
3 DHW Temp Sensor
✓
✓
3a DHW Hdr Sens Point (Item 3 = Network or BAS)
✓
✓
3b DHW Temp Unit Addr (Item 3 =Direct)
✓
✓
4
Rtn Hdr Temp Sensor
✓
✓
✓
4a Return Hdr Sens Point (Item 4 = Network)
✓
✓
✓
5
Outdoor Air Temp Sens
✓
✓
✓
✓
✓
✓
5a BST Outdoor Temp (Item 5
≠ Off)
✓
✓
✓
✓
5b Outdoor Temp Addr (Item 5 = Network)
✓
✓
✓
5c Warm Weather Shtdwn (Item 5
≠ Off)
✓
✓
✓
✓
5d OAT Temp Point (Item 5 = Network)
✓
✓
✓
6 VSP Pump Mode
✓
✓
✓
✓
✓
✓
6a VSP Pump Speed Adjust (Item 6
≠ Off)
✓
✓
✓
✓
✓
✓