Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
39
of
196
•
Enter the upper and lower limits of the DHW setpoint in the
DHW Setpt Low
Limit
and
DHW Setpt Hi Limit
fields.
•
Pressing
Next
takes you to the
Select BAS Mode
Figure 2.3.2.1.2-5: BST Manager
– DHW: DHW Analog Input Screen
4. If you chose
Network
or
BAS
, the
Select BAS Mode
2.3.2.1.3
EZ Setup: BST Manager
–
Other Application
Complete these instructions only if you chose
Other
at the end of Section 2.3.2.
Figure 2.3.2.1.3-1: BST Manager
– Other: Select Your Boiler Application
1. The
Other Operating Mode
screen appears. Choose the operating mode for the
“other”
application, either
Constant Setpoint
or
Remote Setpoint
, then press
Next
to continue.
Figure 2.3.2.1.3-2: BST Manager
– Other: Other Operating Mode Screen