Node Offset
: The starting address range for AERCO units.
•
Device Instance
: Identifies the device on a BACnet network (read-only). It is
generated from the
Node Offset
added to the
Communication Address
field. This
value must be unique on a BACnet network.
•
Port Number
: Specify the BAS port to which the unit will communicate.
(Range: 47808 to 47823)
•
Local IP Address
: Displays the local IP address of the Edge Controller.
•
Status
: Displays the status of BAS communications.
•
Security
: Choose whether to
Enable
or
Disable
BAS Security. This option prohibits
communication to any devices as specified by the IP address and MAC address, per
parameters below. If enabled, the following additional parameters appear:
o
BAS IP
: Specifies the IP address of the BAS server.
o
BAS MAC
: Specifies the MAC address of the BAS server.
•
BAS Temp Format
: Choose
Fahrenheit
,
Celsius
or
Points
.
•
Allow System Disable
: If set to
Yes
(the default), a BAS front-end application can
initiate a system shutdown or an individual unit shutdown by writing
85
to one of the
addresses below via BACnet or Modbus (not available for ProtoNode). The BAS can
reenable the system/unit by sending
0
to the same address.
•
For BACnet
o
BST Manager BACnet address
229
o
BST Client BACnet address
80
•
For Modbus
o
BST Manager Modbus address
40229
o
BST Client Modbus address
40081