Edge [ii] Controller Operation Manual
SECTION 4: DIAGNOSTICS
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
76
of
196
4.1 Manual Run
Most diagnostic test procedure require the unit to be in
Manual Mode
. Putting the Controller in
Manual Mode
does the following:
•
Initially r
educes the unit’s Fire Rate to zero.
•
Allows the system to display certain diagnostic options that are otherwise unavailable.
•
Suppresses event transmissions to external systems.
•
Lights the red
Manual
LED on the Controller
’s front face.
•
Flags all events in the internal log as related to Manual Mode.
To put the unit in Manual Mode:
1. Go to:
Main Menu
→
Diagnostics
→
Manual Run
.
Figure 4.1: Diagnostics: Manual Run Screen
– Manual Mode Enabled
2. Enable the
Manual Mode
toggle.
The red Manual LED lights on the Controller’s front face
turns on, the unit shuts down (if not already) and stays in
Manual Mode
until it is disabled
from this screen, or until the session times-out.
3. When Manual Mode is enabled, the Fire Rate control appears. You can use these controls
to manually fire the unit in 1% increments using the
+
and
–
controls or press on the field
and manually enter a specific fire rate.
4. When you are done operating in
Manual Mode
, use the
Manual Mode
toggle to disable it.
All initiated/active diagnostic routines/processes will terminate, the
Manual
LED on the
Controller
’s front face will go off, and the unit will resume normal operation.