Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
151
of
196
6.5 Ancillary Devices
The
Ancillary Devices
screen allows configuration of all unit inputs and outputs.
1. Go to:
Main Menu
→
Advanced Setup
→
Ancillary Devices
.
Figure 6.5: Advanced Setting: Ancillary Devices Screen
NOTE:
You can navigate from one
Ancillary Device
screen to the next in round-robin fashion using
the
Page Left
and
Page Right
icons on each screen.
6.5.1 Interlocks
The Controller offers two interlock circuits,
Remote Interlock
and
Delayed Interlock
, both of which
can interface with an Energy Management Systems (EMS) or a Building Automation System (BAS)
and auxiliary equipment such as pumps or louvers. Both must be in the closed position to allow
the unit to fire. They must be connected to the following pins
on the unit’s I/O board (see the
Benchmark Platinum-Edge: INSTALLATION Manual
(OMM-0136, GF-210) for more info):
•
Remote Interlock
wired to connector strip J6, pins 1 and 2
•
Delayed Interlock
wired to connector strip J6, pins 3 and 4
1. Go to:
Main Menu
→
Advanced Setup
→
Ancillary Device
→
Interlocks
.
Figure 6.5.1: Ancillary Devices: Interlocks Screen