Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
50
of
196
6. If you chose
Remote Setpoint
in step 4, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.3.2.2.2-8: BST Manager
– DHW & Other: Select Remote Setpoint Type
A. If you chose either
4-20mA
or
0-20mA
, the
Other Analog Input
screen appears.
Configure the following parameters. Pressing
Next
takes you to the
Select BAS
Mode
•
Choose the remote setpoint source in the
Other Rmt Setpt Source
field (a
green border appears on the previous choice, if there was one):
Spare Analog
in 1
,
Spare Analog in 2
,
Spare Analog in 3
.
•
Enter the upper and lower limits of the “other” setpoint in the
BST Other
Setpt Lo Limit
and
BST Other Setpt Hi Limit
fields.
•
Pressing
Next
takes you to the
Select BAS Mode
Figure 2.3.2.2.2-9: BST Manager
– DHW & Other: Other Analog Input Screen
B. If you chose
Network
, the
Select BAS Mode
screen. Skip to