Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
53
of
196
4. If you chose
Outdoor Air Temperature Reset
(OATR) in Step 1, the Select Outdoor Reset
Mode screen appears. Choose the
Outdoor Reset Mode
then press
Next
.
Figure 2.3.2.2.3-6: BST Manager
– SH & Other: Select Outdoor Reset Mode
A. If you chose
Off
, the
Other Operating Mode
screen appears (skip to Step 5).
B. If you chose
Network
,
Direct
or
BAS
, configure following parameters:
•
OAR Min
and
OAR Max
: These four parameters are used to create the
associated OATR curve. Once the curve has been setup, the controller will
compute the setpoint based on outside temperature.
•
Warm Weather Shutdown
: The threshold outside temperature above
which the unit shuts down.
•
Pressing
Next
takes you to the
Other Operating Mode
screen (see Step 5).
Figure 2.3.2.2.3-7: BST Manager
– SH & Other: Space Heating Outdoor Reset