Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
96
of
196
•
Date & Time
: Allows you to set the date and time. The
Time Format
control allows
you to select 12- or 24-hour format.
Figure 6.2.1-2: Unit: Enter Date & Time Screens
•
Time Format
: Choose the
12 Hour
or
24-Hour
format.
•
Vent Type
: Select from unit-type-specific venting options:
PVC
,
cPVC
,
Polypro
or
Stainless
Steel
.
•
Exhaust Safety
: If Enabled, this parameter protects the unit and exhaust vent from
excessively high exhaust temperatures. When exhaust temperature exceeds any of
three limits, an action is taken, as shown in the table below. The limits depend on the
vent material specified in
Vent Type
(Stainless Steel has no limit).
TABLE 6.2.1: Exhaust Safety Temperature Limits
Limit Type
Result Action
Vent Material
PVC
CPVC
Polypro
Caution Limit
Display Warning
158°F
210°F
215°F
High Temp Limit
Reduce Fire Rate
170°F
220°F
220°F
Fault Limit
Unit Shut Down
180°F
230°F
230°F
•
Fuel Type
or
Primary Fuel
(Dual Fuel models only): Choose either
Natural Gas
or
Propane
. This option is not available for all unit types.
•
Secondary Fuel
(Dual Fuel models only): Displays the alternative to
Primary
Fuel
.
•
Blower RPM Display
:
If set to
Enabled
the following parameter appears:
o
Blower Pulses/Rev
: Specifies the number of blower pulses per revolution,
based on the tachometer output of the blower. Setting above 0 is only practical in
units with blowers that have a tachometer output. (Range: 0 to 100)
•
Language
: Choose from available language options:
English
,
Spanish
,
French
.
•
Unit of Measurement
: Choose the unit of measure the Controller will use, either
Metric
(°C, lps, Pa) or
English
(°F, gpm, in. W.C., psi). The corresponding LED
indicator on the Controller’s front face, °F or °C, lights (see Figure 6.2.2-1, below).
•
Temperature Sensor
: Specifies the sensor type:
PT1000
(the default on all
current units) or
Balco
. DO NOT CHANGE unless replacing a C-More Controller on
legacy units equipped with Balco sensors.