Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
48
of
196
1. The
DHW Operating Mode
screen appears. Choose the
DHW Operating Mode
, either
Constant Setpoint
or
Remote Setpoint
. Press
Next
to continue.
Figure 2.3.2.2.2-2: BST Manager
– DHW & Other: DHW Operating Mode Screen
2. If you chose
Constant Setpoint
in Step 1 specify the
Setpoint
for the domestic hot water
application.
When you press
Next
the
Other Operating Mode
screen appears (skip to Step
4, below).
Figure 2.3.2.2.2-3: BST Manager
– DHW & Other: DHW Constant Setpoint Screen
3. If you chose
Remote Setpoint
in step 1, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.3.2.2.2-4: BST Manager
– DHW & Other: Select Remote Setpoint Type
A. If you chose either
4-20mA
or
0-20mA
, the
DHW Analog Input
screen appears.
Configure the following parameters:
•
Choose the remote setpoint source in the
DHW Rmt Setpt Source
field
(the previous choice, if there was one, has a green border):
Spare Analog in
1
,
Spare Analog in 2
or
Spare Analog in 3
.