Edge [ii] Controller Operation Manual
SECTION 3: CALIBRATION
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
69
of
196
3.3.3 Analog Inputs
The
Analog Inputs
screen allows you to calibrate all the available analog inputs, such as a
sensor, a remote signal, or feedback from a device such as a valve. If reliable feedback or
external instrumentation indicates the reading is inaccurate, you can adjust its reading via the
Offset
parameter. This process can be repeated for all available analog inputs.
Figure 3.3.3: Input/Output: Analog Inputs Screen
1. Go to:
Main Menu
→
Calibration
→
Input/Output
→
Analog Inputs
.
2. Press the
Analog Name
field and choose the sensor you want to view. The selected input
is displayed along with its current reading. The available Analog Inputs are:
•
CO/Analog In
•
Air Pump
•
Spare Analog In 3
•
Spare Analog In 2
•
Flow
•
Remote Analog In
•
Spare Analog In 1
•
Cas Vlv Fdbk (Cascade Valve Feedback)
3. If you chose
Remote Analog In
or
Spare Analog In
1
,
2
or
3
in step 2, the
Function
parameter appears with a read-only display of the function to which the input is currently
assigned (assignments are made in
•
DHW Setpoint
•
Swing V1 Feedback
•
Swing V2 Feedback
•
Blr VSP Feedback
•
DHW VSP Fdbk
•
SmartPlate VP
•
NOx
•
Other Setpoint
4. This screen includes the following additional parameters:
•
Board Reference
: Displays how the input connects to the Edge Controller, either
through the
unit’s wiring harness or to specific pins on the unit’s I/O Board (see the I/O
board map in Section 2.11 of the
Benchmark Platinum-Edge Installation Manual,
OMM-
0136, GF-210).
•
Offset
: If necessary, you can adjust the
Current Reading
to match a reliable reading
or instrument by entering a value in this parameter. (Range: -2.0 to +2.0, default = 0.0)
•
Current Reading
: A read-only display of the current value. If no input is sensed, it
displays either
INVALID
or --- (blank).
5. You can repeat Steps 2 through 4 with the other Analog Inputs, as needed.