Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
40
of
196
2. If you chose
Constant Setpoint
, specify the
Other Setpoint
. Pressing
Next
takes you to
the
Select BAS Mode
screen; skip to
instructions.
Figure 2.3.2.1.3-3: BST Manager
– Other: Other Heating Constant Setpoint Screen
3. If you chose
Remote Setpoint
in step 1, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.3.2.1.3-4: BST Manager
– Other: Select Remote Setpoint Type Screen
A. If you chose either
4-20mA
or
0-20mA
, the
Other Analog Input
screen appears. Fill
in the parameters listed below.
•
Press
Other Rmt Setpt Source
and choose the source of the remote
setpoint (the previous choice, if there was one, has a green border):
Spare
Analog in 1
,
Spare Analog in 2
or
Spare Analog in 3
.
•
Enter the upper and lower limits of the “other” setpoint in the
BST Other
Setpt Lo Limit
and
BST Other Setpt Hi Limit
fields.
•
Pressing
Next
takes you to the
Select BAS Mode