Edge [ii] Controller Operation Manual
SECTION 7
– UNIT STATUS
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
175
of
196
7.4 BST Cascade Status
The
BST Cascade Status
screen provides a view of the BST cascade as a whole. It displays
the status of all of the 16 possible boilers, as well as pertinent BST system settings and
readings.
This screen is displayed in round-robin fashion only on the BST Manager unit.
Figure 7.4-1: BST Cascade Status Screen
The following notes apply to this screen:
•
The data displayed on this screen depends on the Application(s) chosen in
. It can display data for only two applications at a time,
Space
Heating
and
DHW
, or
Other
.
•
Each of the 16 possible boilers in the BST cascade is represented by a box in the grid
and identified by their COM Address. Unused boxes are shown blank.
•
The color of Lead boiler box blinks on/off.
•
The colors of the box and the text in the boxes display the designation and status of each
boiler within the BST cascade:
Unit Designations
Unit Status
Label
Description
Label
Status
Color
DS
Dedicated Space Heating
Off Line
BLACK
DD
Dedicated DHW
DIS
Disabled
GREY
SS
Swing Boiler - SH
FLT
Fault
RED
SD
Swing Boiler - DHW
STBY
Standby
WHITE
Sd
Swing Boiler, serving
DHW, default SH
ON
Operating
GREEN
Ss
Swing Boiler, serving SH,
default DHW
S LIM
Setpt Lim
AMBER
IGN
Igniting
WHITE
•
The Lag unit displays
LAG
in place of the COM Address.