Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
35
of
196
1. The
SH Operating Mode
screen appears. Choose the
Operating Mode
for the Space
Heating application,
then
press
Next
to continue:
•
Constant Setpoint
•
Remote Setpoint
•
Outdoor Air Temperature Reset
(OATR)
Figure 2.3.2.1.1-2: BST Manager
– Space Heating: SH Operating Mode Screen
NOTES:
•
If the outdoor air sensor is not connected, the display of the
OAT
(Outdoor Air
Temperature) at the bottom of the screen is disabled.
•
If the header sensor is not connected, the bottom of the screen
displays
HDR = --- °F
. For
the header sensor to function without previous setup, the default for
Outdoor Air Temp
Sens
parameter must set to
Direct
2. If you chose
Constant Setpoint
in step 1, specify the
SH
Setpoint
. Pressing
Next
takes
you to the
Select BAS Mode
screen; skip to
instructions.
Figure 2.3.2.1.1-3: BST Manager
– Space Heating: Constant Setpoint Screen