Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
148
of
196
6.4.2 onAER
The
onAER
screen allows you to choose and configure how onAER will communicate with the
network.
1. Go to:
Main Menu
→
Advanced Setup
→
Comm & Network
→
onAER
.
Figure 6.4.2: Comm & Network: onAER Screen
2. The
onAER Mode
parameter’s default is
Disabled
. To enable onAER communication,
choose one of the following:
•
Ethernet
: Requires an Ethernet cable to
plugged into the Controller’s left side, as
shown in Figure 6.2.7.1-1, in Section 6.2.7.1.
•
Wi-Fi
: Requires the AERCO Wi-Fi module (P/N 24526-TAB) to be installed on the unit;
see the
onAER Wi-Fi Module Installation
Guide
(TID-0178) for instructions.
•
Wiznet
: This option intended for units on which the Edge Controller was installed as a
replacement for the C-More Controller.
3. Once enabled, the following additions parameters appear:
•
Unit Upload Time
: This determines how frequently unit data will upload to the server,
in seconds. This will be split between unit data and cascade data (manager unit only).
(Range: 30 to 9999)
•
Cascade Upload Time
: Determines how cascade data will upload to the server, in
seconds. (Range: 60 to 9999)
•
Status
:
Displays the communication interface status, which varies depending on the
interface selected in Step 2.